Lightning Current Impulse IEEE and IEC
8/20 current impulse with limits on the adjustment of equipment such that the measured values are from 7 µs to
9 µs for the virtual front time and from 18 µs to 22 µs for the time to half-value on the tail
NOTE The time to half-value on the tail is not critical and may have any tolerance during the residual
voltage type tests.